110/220 or 120/240?
110 volt and 220 volt designations are old familiar terminology, but are no longer commonly used in either product design or by electric utilities.
The 115 volt and 230 volt terminology comes from equipment design standards. Equipment is usually designed to operate at 115 or 230 volts with a plus or minus 10% acceptable variation.
Utility companies deliver electric service at 120 / 240 volts plus or minus 5%.
Thus, the correct terms are usually 120 and 240, but for practical purposes 110=115=120 and 220=230=240.
AFCI – Arc Fault Circuit Interrupter
AFCI Breakers are designed to protect your home from fires which are cause by arcing as well as over current conditions. Normal breakers are only effective against over current conditions. Arc Fault Breakers are now required by new construction codes to protect receptacles which are located in bedrooms (and possibly other locations according to local codes variants). Arc Fault breakers may not be 100% effective against all fires caused by arcing because there is a certain amount of arcing which is normal, and the arc fault breaker would be unusable if it tripped every time that a normal arc were detected. For example if you ever noticed a spark when you unplug an appliance or flipped a wall switch, then that is normal arcing. Abnormal (and Dangerous) arcing often is caused by a poor connection, or damaged wire. Unfortunately, dangerous arcing “looks” an awful lot like normal arcing to the breaker, so it is possible for a fire to be started without tripping the breaker. Nonetheless an arc fault breaker, even if less than perfect, is a lot better than no protection at all. By the way, arc faults are one of the big reasons that electrical connections should never be made outside of an approved wiring device.
Arc Fault Breakers like GFI devices have “test” and “reset” buttons and should be tested periodically according to the manufacturer’s specifications (usually once a month).
Approved Wiring Device
This term refers to any of a number of devices which are “approved” by Underwriters Laboratory or some other codes sanctioned testing organization for the purpose of mounting electrical fixtures and equipment, or for containing connections. Appliances and some fixtures are considered as approved wiring devices also. Wiring supply connections may only be made inside of approved wiring devices, and for several good reasons. The wiring device protects the connection from tampering, abrasion or other damage, and also protects the home from electrical fires which are most likely to start at connections.
Buck Boost Transformer
is a small single phase transformer which reduces (buck) or raises (boost) line voltage a small amount. The most common example is boosting 208 volts (derived from 3 phase service) to 230 volts (equivalent to single phase service) to operate a 230 volt appliance such as an HVAC compressor or fan motor from a 208 volt supply line. A buck-boost transformer does not alter the phase signature of the power supply.
GFCI devices
GFI or GFCI (Ground Fault Circuit Interrupter) devices help to protect people from being shocked or electrocuted. They work by very quickly detecting a “Ground Fault” (for example the ground fault that happens when a person is being shocked, one caused by a short, or a voltage “leak” caused by dampness in and around electrical equipment) and interrupting the current. GFI devices are usually either in the form of a receptacle or a breaker, although some equipment (hot tubs for example) may sometimes have GFI protection built in, but not usually. A single GFI receptacle or breaker often protects many additional receptacles or fixtures, which sometimes causes confusion because a homeowner doesn’t know that a tripped GFI receptacle in another part of the house could be interrupting the current to a regular receptacle.
In many codes jurisdictions an old fashioned two prong outlet can be replaced with a three pronged GFI receptacle in order to safely allow the use of modern appliances with three pronged plugs. GFI protected circuits and devices are usually found (and required by codes) outside, and in damp locations such as bathrooms, kitchens, and basements. Wet conditions around a GFI protected device may trigger the GFI and prevent it from being reset able.
All GFI devices have “Test” and “Reset” buttons on them. The test button causes a ground fault within the device and trips the reset button causing it to pop out and protrude slightly, thus interrupting the current to any devices which are protected by the GFI in question. Pushing the reset button in until it catches will restore current to the circuit. If the “test” button fails to function as described then the GFI device must be replaced. As mentioned previously, a continuous ground fault (like one cause by excessive water around the electrical equipment) will prevent the GFI from being reset able, and must be remedied before the circuit will be usable. A nonfunctioning GFI device is an extremely dangerous situation, which must be remedied immediately.
Ground loop
All residential electrical systems should have a single point ground. Grounding to multiple places will cause all kinds of problems with noise, hum, snow, and generally bad audio video signals. Intuitively it would seem that having redundant grounds would be a good thing, but it is not, because voltage is a relative value. If you did an experiment where you connected a long conductor to your house current, and then checked the voltage to ground at different locations (different places in the yard, water pipes, the ground rod, etc..) you would find that there would be different voltage potentials at different spots. In fact if you measured the voltage potential between two spots of earth in the yard you might find that current would actually flow through a conductor between two spots of earth. Those different voltage potentials and the current they cause are why ground loops are bad. Especially troublesome ground loops can be cause when a length of coaxial wire connects two pieces of audio video equipment (cable box, TV, etc…) which are plugged into different outlets. One great way to fix this problem is to use surge protectors which incorporate coax protection.
Line
An electrical term which is short for “line voltage” and indicates wires which bring power into a device, and the terminals that such wires connect to. Incoming Power.
Load
An electrical term which indicates an additional electrical load, the wires that carry current from a device to the load, and the terminals on a device that such wires connect to. Outgoing power.
Wild-leg
Wild-wire or red-leg delta properly referred to as high leg delta is a type of three phase transformer winding connection sometimes found in older electrical installations. A transformer wound in this fashion will have four wires coming out of the secondary: the three phases, plus a neutral that is a center-tap of one of the windings. The voltages between the three phases are relatively the same; however the voltage magnitudes between a particular phase and the neutral vary. The phase-to-neutral voltage of two of the phases will be half of the phase-to-phase voltage. The remaining phase-to-neutral voltage will be 1.7 times the phase-to-phase voltage. Typically, the transformer is designed such that the ‘B’ phase is the ‘high’ leg. According to Article 110.15 of the 2005 National Electrical Code, panel boards connected to this type of transformer must explicitly identify as the high leg, preferably by coloring it orange. Generally the high-leg can not be used for loads requiring a neutral such as lighting because of the high voltage potential. In other cases such as three phase motors which do not utilize a neutral the wild-leg is irrelevant because it has the same phase to phase voltage potential as the other two legs.
I enjoyed reading through your website very much and found it exceptionally helpful. In fact, I read and studied over all of your articles except for the ceiling fan installation notes that I pretty much had covered. Your simple solution to replacing old style two wire outlets with new two wire w/ground outlets was especially helpful. I’ve been perplexed on how to solve this problem; indeed, I have several cracked (obviously dangerous) old outlets that I didn’t know how to safely replace. Our electrical inspector didn’t suggest this solution, so I suspect that it’s not quite up to local code, but it is certainly safer than retaining the old, damaged outlets. Thanks very much for the free information. No need to reply to my comments; I just wanted to take a moment to thank you for providing this free information and for fulfilling the original promise of the www before everything became over commercialized. Cheers, Michael
Hey, I have found this most helpful. I was wondering if any thing was added to the code book about fire caulking and also if receptacles are allowed to be higher than the standard hieght in any application.
Electrical fires are extremely common, and can spread very quickly, resulting in walls that are destroyed within minutes.
These types of fire usually happen because the wires and circuits are either overloaded or faulty.
The wiring and circuits used are outdated or, most common with home repairs, the wires and circuits are improperly installed.
Consider, too, that improper wiring can easily damage your major home appliances.
Do you really want to replace your fridge because you messed up on the wiring? Probably not!
I have a 220 circuit that has a female wall plug in with the two hot slots on a slant and the ground as an L shaped slot. The dryer cord has the same shaped hot prongs but has a single flat blae.
Are there code restrictions for the amperage that are refleted in the shape of the wall socket? How about a page with pictures or diagrams of the different types and the amperage for each?
“ayment-protection-insurance-2/ Thanks for that awesome posting. It saved MUCH time
It is a capital in that full-size quest properly-suited content materials, I will ponder to exculpate. The ammo is so significantly organized that readers swear by amusing me jargon impress for germane seconds. alimony genuine addition.
Good morning, thanks alot : ) for a particularly enjoyable
article, I really don’t normally submit remarks but really enjoyed your blog thus felt I would say thanks for your insight ~ Rosie
Everything is very open with a very clear explanation of the challenges.
It was really informative. Your site is useful. Thanks for sharing!
“Construction and Electrical Wiring Terms
Defined | No-Jolt” was a good read and I was really pleased to
find the blog post. Thanks,Mitch
Hi there, this weekend is nice for me, since this occasion
i am reading this wonderful informative post here at my residence.
Please let me know if you’re looking for a writer for your blog. You have some really good articles and I believe I would be a good asset. If you ever want to take some of the load off, I’d absolutely love to write some material for
your blog in exchange for a link back to mine. Please
shoot me an e-mail if interested. Thanks!
Somebody necessarily assist to make critically posts I would state. This is the first time I frequented your website page and thus far? I amazed with the research you made to create this actual submit extraordinary. Great process!
Can I just say what a relief to find an individual who actually knows what theyre talking about on the internet. You truly know how to bring an issue to light and make it important. Much more men and women must read this and understand this side in the story. I cant feel youre not more well-known due to the fact you actually have the gift.
This is a great job. Keep doing this. Also liked your previous write either…
Thanks for your inquiry. That’s really cool. Please keep moving like this.
Hey there! This is my first comment here so I just wanted to give
a quick shout out and tell you I really enjoy
reading through your articles. Can you suggest
any other blogs/websites/forums that deal with the same topics?
Thank you!
Undeniably believe that which you stated. Your favorite justification appeared to
be on the internet the easiest thing to be aware of. I say to you, I definitely get irked while people consider worries that they plainly don’t know about. You managed to hit the nail upon the top as well as defined out the whole thing without having side effect , people can take a signal. Will likely be back to get more. Thanks
My husband and i felt absolutely delighted Jordan managed to deal with his preliminary research using the ideas he got when using the web page. It is now and again perplexing to simply possibly be giving away methods which most people could have been making money from. And we grasp we have the writer to give thanks to because of that. Those explanations you’ve made, the simple site navigation, the friendships your site make it easier to promote – it’s many astonishing, and it is helping our son and the family know that this issue is awesome, and that’s seriously pressing. Many thanks for all the pieces!